Pyroelectric fire alarm
Here
is an ultra-sensitive fire sensor that exploits the direct
piezoelectric property of an ordinary piezo element to detect fire. The
lead zirconate titanate crystals in the piezo element have the property
to deform and generate an electric potential when heated, thus
converting the piezo element into a heat sensor. The circuit described
here is very sensitive. It gives a warning alarm if the room temperature
increases more than 10°C
Sensor
side circuit. Fig. 1 shows the fire sensor circuit. The front end of
the circuit has a sensitive signal amplifier built around IC1 (CA3130).
It gives a high output when temperature near the piezo element
increases. IC CA3130 is a CMOS operational amplifier with gate protected
p-channel MOSFETs in the inputs. It has high speed of performance and
low input current requirements. There are two inputs—the non-inverting
input (pin 3) connected to the piezo element through diode D7
(OA71) that carries the voltage signal from the piezo element and the
inverting input (pin 2) that gets a preset voltage through VR1.
By adjusting VR1, it is easy to set the reference voltage level at pin
2. In normal condition, IC1 gives a low output and the remaining
circuitry is in a standby state. Capacitor C2 keeps the non-inverting
input of IC1 stable, so that even a slight change in voltage level in
the inputs can change the output to high.Normally, IC1 gives a low
output, keeping transistor T1 non-conducting. Reseting pin 12 of IC2
(CD4060) connected to the collector of transistor T1 gets a high voltage
through R5 and IC2 remains disabled. When the piezo element gets heat
from fire, asymmetry in its crystals causes a potential change, enabling
capacitor C2 to discharge. It momentarily changes the voltage level at
pin 3 of IC1 and its output swings high. Transistor T1 conducts taking
the reset pin 12 of IC2 to ground. IC2 is now enabled and starts
oscillating. With the shown values of the oscillating components C3
(0.22μ) and R6 (1M), the first output (Q3) turns high after a few
seconds and a red LED2 starts flashing. If heat near the piezo persists,
Q7 (pin 14) output of IC2 becomes high after one minute, and the alarm
starts beeping. If heat continues, Q9 (pin 15) turns high after four
minutes and turns on the relay driver transistor T2. At the same time,
diode D8 conducts and IC2 stops oscillating and toggles.
The
solenoid pump connected to the N/O (normally opened) contact of the
relay starts spraying the fire-ceasing foam or water to the possible
sites of fire.
Power
supply circuit. Power supply section (Fig. 2) comprises a 0-12V, 1A
step-down transformer with a standard full-wave rectifier formed by D1
through D4 and filter capacitor C1. A battery backup is provided if the
mains supply is cut-off due to short-circuit and fire. A 12V, 4.5Ah
rechargeable battery is used for backup to give sufficient current to
the solenoid pump. When mains
power
is available, diode D5 forward biases. It provides power to the circuit
and also charges the battery through resistor R2, and it limits the
charging current to 120 mA. When power fails, diode D5 reverse biases
and diode D6 forward biases, giving instant backup to the circuit. LED1
indicates the availability of mains power.
Assemble
the circuit on a generalpurpose PCB and enclose it in a suitable case.
Connect the piezo element to the circuit using a thin insulated wire.
Glue the flat side of the piezo element on a 30×30cm aluminium
sheet to increase its sensitivity. Fix the sheet with the piezo sensor
to the site where protection is needed. The remaining circuit can be
fixed at a suitable place. If only the alarm generator is needed, omit
the relay driver section.
0 comments: